Fire Alarm Control Panel
A Fire Alarm Control Panel (FACP), or Fire Alarm Control Unit (FACU), is the controlling
component of a Fire Alarm System. The panel receives information from environmental
sensors designed to detect changes associated with fire, monitors their operational
integrity and provides for automatic control of equipment, and transmission of information
necessary to prepare the facility for fire based on a predetermined sequence. The
panel may also supply electrical energy to operate any associated sensor, control,
transmitter, or relay. There are four basic types of panels: coded panels, conventional
panels, addressable panels, and multiplex systems.
Coded fire alarm control panels
Coded panels were the earliest type of central fire alarm control, and were made
during the 1800s to the 1970s. A coded panel is similar in many ways to a modern
conventional panel (described below), except each zone was connected to its own
code wheel ( i.e. An alarm in zone 1 would sound code 1-2-4 [through the bells or
horns in the building], while zone 2 would sound 1-2-5), which, depending on the
way the panel was set up, would either do sets of four rounds of code until the
initiating pull station was reset (similar to a coded pull station) or run continuously
until the panel itself was reset. Large panels could take up an entire wall in a
mechanical room, with dozens of code wheels. Lists of codes had to be maintained,
sometimes with copies posted above pull stations (this setup is commonly seen in
older wings of hospitals). Smaller panels could be set up in one of two ways. Most
of the time, the panel would only have one zone, and therefore, only one code. Common
one-zone codes were 4-4-0 and 17-0-0 (which is similar to the 120 bpm March Time
setting used on later panels, which has in turn been replaced with an interrupted
four count uniform temporal code 3 pattern used since 1996). Alternatively, the
panel could be made with no code wheels, using only what was called the gong relay.
Normally, this would be used in a system with coded pull stations to retransmit
the coding strikes from the pulls. However, it could also be used as its own zone,
with the connected horns or bells sounding continuously instead of in a particular
code. These panels are not common today, but can sometimes be found in older buildings
such as those on college campuses or hospitals. Today, there are two types of fire
panels:
-
Conventional
fire alarm panel;
-
Addressable fire alarm panel
Conventional fire alarm control panels
Conventional panels have been around ever since electronics became small enough
to make them viable. Conventional panels are used less frequently in large buildings
than in the past, but are not uncommon on smaller projects such as small schools,
stores, restaurants, and apartments. A conventional Fire Alarm Control Panel employs
one or more circuits, connected to sensors (initiating devices) wired in parallel.
These sensors are devised to dramatically decrease the circuit resistance when the
environmental influence on any sensor exceeds a predetermined threshold. In a conventional
fire alarm system, the information density is limited to the number of such circuits
used. To facilitate location and control of fire within a building, the structure
is subdivided into definite areas or zones. Floors of a multistory building are
one type of zone boundary. An Initiating Device Circuit connected to multiple devices
within the same "zone" of protection, effectively provides 2 bits of information
about the zone corollary to the state of the circuit; normal, or off normal and
alarm or quiescent. The state of each Initiating Device Circuit within a zone displays
at the Fire Alarm Control Panel using visible indications called Annunciators. These
Annunciators may employ a graphical representation of the Zone boundaries on a floor
plan (Zone map) using textual descriptions, illuminated icons, illuminated sections,
or illuminated points on the map corresponding to Initiating Circuits connected
to the Fire Alarm Control Panel. For this reason, slang often inaccurately refers
to initiating circuits of a Fire Alarm Control Panel as Zones. Larger systems and
increasing demand for finer diagnostic detail beyond broad area location and control
functions expanded the control by Zone strategy of conventional systems by providing
multiple initiating circuits within a common Zone, each exclusively connected to
a particular type of initiating device, or group of devices. This arrangement forms
a device type by Zone matrix whose information is particularly suited to the Tabular
Annunciator In multistory buildings employing a Tabular Annunciator for Example;
rows of indicators define the floors horizontally in their stacked relationship
and the type of device installed on that floor displays as columns of indicators
vertically aligned through each floor. The intersection of the floor and device
indicators provides the combined information. The density of information however
remains a function of the number of circuits employed. Even larger systems and demands
for finer diagnostic and location detail led to the introduction of addressable
fire alarm systems with each addressable device providing specific information about
its state while sharing a common communication circuit. Annunciation and location
strategies for the most part remain relatively unchanged.
A wiring diagram for a simple fire alarm system consisting of two input loops (one
closed, one open)
Multiplex systems
Multiplex systems, a sort of transition between conventional and modern addressable
systems, were often used in large buildings and complexes from the mid to late 1970s
into the late 1980s. Early on, these systems were programmed to function as large
conventional systems. Gradually, later installations began to feature components
and features of modern addressable systems. These systems were often capable of
controlling more than a building's fire alarm system (i.e. HVAC, security, electronic
door locks...) without any type of alarm or trouble condition present. While the
main panel was the brains of the system and could be used to access certain functions,
fire alarm controls were usually accessed through transponders. These were smaller
conventional panels programmed to 'communicate' the status of part of the system
to the main panel and also could be used to access basic fire alarm control functions
Releasing panels
Releasing panels are capable of using solenoids to disperse fire-fighting chemical
agents such as halon or water from piping located throughout a building. A releasing
panel usually will have a manual abort switch to abort an accidental release which
could damage property or equipment. Releasing capability can be part of both addressable
and conventional panels.
Addressable Fire Alarm Control Panels
Addressable panels are usually more advanced than their conventional counterparts,
with greater information capacity and control flexibility. Addressable fire alarm
panels were introduced by many manufacturers during the microcontroller boom in
the mid-1980s.
Signaling Line Circuits
Addressable Fire Alarm Control Panels employ one or more Signaling Line Circuits,
slang - usually referred to as loops or SLC loops - ranging between one and thirty.
Depending on the protocol used, a Signaling Line Circuit can monitor and control
several hundred devices. Some protocols permit any mix of detectors and input/output
modules, while other protocols have 50% of channel capacity restricted to detectors/sensors
and 50% restricted to input/output modules. Each SLC polls the devices connected,
which can number from a few devices to several hundred, depending on the manufacturer.
Large systems may have multiple Signaling Line Circuits. Each device on a SLC has
its own address, and so the panel knows the state of each individual device connected
to it. Common addressable input (initiating) devices include
-
Smoke detectors
-
Heat Detectors (Rate of Rise and Fixed Temperature)
-
Manual call points or manual pull stations
-
Notification appliances (Simplex systems with True Alert signals only)
-
Responders
-
Fire sprinkler system inputs
-
Switches
-
Flow control
-
Pressure
-
Isolate
-
Standard switches
Addressable output devices are known as relays and include
-
(Warning System/Bell) Relays
-
Door Holder Relays
-
Auxiliary (Control Function) Relays
Relays are used to control a variety of functions such as
-
Switching fans on or off
-
Closing/opening doors
-
Activating fire suppression systems
-
Activating notification appliances
-
Shutting down industrial equipment
-
Recalling elevators to a safe exit floor
-
Activating another fire alarm panel or communicator
Mapping
Also known as "cause and effect" or "programming", mapping is the process of activating
outputs depending on which inputs have been activated. Traditionally, when an input
device is activated, a certain output device (or relay) is activated. As time has
progressed, more and more advanced techniques have become available, often with
large variations in style between different companies.
Zones
Zones are usually made by dividing a building, or area into different sections.
Then depending on the specific zone, a certain amount and type of device is added
to the zone to perform its given job.
Groups
Groups contain multiple output devices such as relays. This allows a single input,
such as a smoke detector or MCP, to have only one output programmed to a group,
which then maps to between two to many outputs or relays. This enables an installer
to simplify programming by having many inputs map to the same outputs, and be able
to change them all at once, and also allows mapping to more outputs than the programming
space for a single detector/input allows.
Boolean logic
This is the part of a fire panel that has the largest variation between different
panels. It allows a panel to be programmed to implement fairly complex inputs. For
instance, a panel could be programmed to notify the fire department only if more
than one device has activated. It can also be used for staged evacuation procedures
in conjunction with timers.
Networking
Although quasi-standards exist that allow panels from different manufacturers to
be networked with each other, they are not in favor with a lot of companies. One
of the most common protocols used is BACnet which is common for various type of
industrial networks. At least one system manufacturer, The Mircom Group of Companies
provides a networkable Fire Alarm Control Panel with a BACnet interface allowing
non-proprietary interoperability of the Fire Alarm Control Panel FACP with other
building systems. Typical interconnected systems to the Fire Alarm Control Panel
include HVAC, Building Automation Controllers, Security/Access Control or Elevator
Controllers. Interoperable systems greatly reduce the long term maintenance cost
of a system and can provide greater emergency response than proprietary offerings.
The Arcnet protocol has been used for years in industrial applications and it is
also used for networking Fire Alarm Control Panels. More recently, some panels are
being networked with standard Ethernet, but this is not yet very common. Most organizations
choose to create their own proprietary protocol, which has the added benefit of
allowing them to do anything they like, allowing the technology to progress further.
However, a bridging layer between the proprietary network and BACnet is usually
available. Networking may be used to allow a number of different panels to be monitored
by one graphical monitoring system.
Monitoring
In nearly every state in the USA, and some other countries the International Building
Code requires fire alarm and sprinkler systems to be monitored by an approved supervising
station. A fire alarm system consists of a computer-based control connected to a
central station. The majority of fire alarm systems installed in the USA are monitored
by a UL listed or FM Global approved supervising station. These systems will generally
have a top level map of the entire site, with various building levels displayed.
The user (most likely a security guard) can progress through the different stages.
From top level site → building plan → floor plan → zone plan, or however else the
building's security system is organized. A lot of these systems have touch screens,
but most users tend to prefer a mouse (and a normal monitor), as it is quite easy
for a touch screen to become misaligned and for mistakes to be made. With the advent
of the optical mouse, this is now a very viable option.
System functions
There are many functions on a fire alarm panel. Some of these are:
System reset
This resets the panel after an alarm condition. All initiating devices are reset,
and the panel is cleared of any alarm conditions. If an initiating device is still
in alarm after the system is reset, such as a smoke detector continuing to sense
smoke, or a manual pull station still in an activated position, another alarm will
be initiated. A system reset is often required to clear supervisory conditions.
A system reset does not usually clear trouble conditions. Most trouble conditions
will clear automatically when conditions are returned to normal. On UK and most
US panels, a "Silence" or "Acknowledge" is usually required before a "System Reset"
can be performed.
Acknowledge
This function, also abbreviated to "ACK", is used to acknowledge an abnormal situation
such as an alarm, trouble or supervisory.
Drill
Also known as "manual evacuation" or "evacuate". On panels that have this function,
the drill function activates the system's notification appliances, often for purposes
of conducting a fire. Using the drill function, an alarm is normally not transmitted
to the fire department or monitoring center. However, building personnel often notify
these agencies in advance in case an alarm is inadvertently transmitted.
Walk test
Walk test allows the functional testing of the system's devices without the assistance
of additional people at the control panel itself. It is also designed to allow initiating
devices to be tested without setting off the building's alarms. Most panels offer
the option for a silent walk test (no alarms activate) or an audible walk test (alarms
activate for a brief period when a device is initiated). A system trouble is typically
generated while the panel is in walk test mode. On European panels, this is usually
an engineer-only function and cannot be activated by the user.
Signal silence
Also known as "alarm silence" or "audible silence". Depending on the configuration
of the alarm system, this function will either silence the system's notification
appliances completely, or will silence only the audible alarm, while strobe lights
continue to flash. Audible silence allows for easier communication amongst emergency
responders while responding to an alarm. This can also be used during construction
as a means of a preliminary test, before the final full test.
Lamp test
Also known as "flash test". This button is known to have become obsolete, but is
still used on many panels. This function is used to check the condition of the LEDs
themselves. A "Lamp Test" button is required by code on multi-zone panels installed
in Canada. Many panels do a lamp test when the system is reset.
Alarm circuit supervision
Various forms of alarm circuit supervision have been used to indicate trouble with
an alarm circuit. Possible alarm circuit faults on a two wire circuit include one
of the conductors being shorted to ground, open circuit (conductor continuity break),
or a short circuit between the conductors. Also the circuits could be tampered with
by having an external AC or DC voltage applied with various duty cycles or waveforms.
There are a number of US patents that address this issue and some have been implemented
in available system products. One of the first to address this issue was Patent
No. 3,588,890 "Resistance Sensing Supervisory System" issued on June 28, 1971 and
assigned to General Motors Corporation. General Motors used this supervision on
all circuits installed in GM plants starting in 1970. An improvement to this basic
"Resistance Sensing Supervisory System" can be obtained by providing a pulsed or
time dependent variable voltage applied to the alarm circuit and is addressed in
US patent numbers 4,030,095 and 4,716,401
Panel alerting
Many panels today have the capability of alerting building personnel of a situation
which can arise into a potentially serious problem. Fire alarm panels indicate an
abnormal condition via a solid or flashing LED. Some panels also contain a small
sounder, used in conjunction with the visual alert. A number of indicators are shown
below. Note that not all fire alarm panels have all of these indicators.
Alarm
Also known as "Fire" or "General Alarm". This indicator is lit when an alarm condition
exists in the system, initiated by smoke detectors, heat detectors, sprinkler flow
switches, manual pull stations, manual call points, or otherwise. Along with the
indicator on the panel, notification appliances, such as horns and strobes, are
also activated, signaling a need to evacuate to building occupants. In an alarm
condition, the fire alarm panel indicates where the alarm originated. The alarm
panel can be reset once the device which initiated the alarm is reset, such as returning
the handle of a manual pull station to its normal position.
Audible silence
The Audible Silence indicator is used in conjunction with the "Alarm" indicator.
It indicates that the fire alarm panel is still in an alarm condition, but that
notification appliances have been silenced. While the alarm is silenced, other functions
in an alarm condition continue to operate, such as emergency service for elevators,
stairway pressurization, and ventilation functions. A new alarm initiation while
the alarm is silenced will take the panel out of Audible Silence and reactivate
the notification appliances.
Report
Also known as "Brigade Called". This indicator is activated when emergency responders
have been automatically notified by the fire alarm system. A variant of this LED
known as "kissoff" activates when the monitoring center replies back to the panel,
indicating a successful communication. Requirements vary depending on jurisdiction
regarding whether a direct connection to the fire department is required, optional,
or prohibited. If a connection to the fire department is optional, or is prohibited,
a fire alarm system is often connected to a monitoring center at the building owner's
discretion.
Drill
Also known as "Manual Evacuation" or "Evacuate". On panels containing this function,
the "Drill" indicator shows that the alarm condition was activated from the fire
alarm panel, often in order to conduct a fire drill. When an alarm is initiated
for a drill, the fire department or monitoring company is usually not notified automatically.
Pre alarm
This LED is often used in conjunction with a two-stage system, in which the panel
requires two devices to be activated (and/or a predetermined time limit to run out
after one device is activated) in order to go into full alarm. This is mostly used
in areas where false alarms are a common problem, or in large applications (such
as hospitals) where evacuating the entire building would not be efficient. The pre
alarm LED is lit when one device has tripped. The pre alarm LED may also be used
if an analog smoke detector registers low levels of smoke in the detection chamber,
but not enough to trigger a full alarm. Depending on the system's layout, the NAC's
may or may not activate for pre alarm conditions. In a two-stage system, the NAC's
are typically coded to a special first-stage coding, or in some situations where
a loud alarm signal could be disruptive, chimes will activate. If there is a voice
evacuation system, it will usually instruct building occupants to await further
instructions while the alarm is being investigated.
Priority 2 alarm
Also known as "Security". This LED can only activate if there is a secondary device
hooked into the "Priority 2 Alarm" terminals. This secondary device could be a security
system, building management system, or another fire alarm control panel. Depending
on how the panel is programmed, the panel's alarms may or may not activate when
a condition like this is present.
Trouble
Also known as "Fault" or "Defect". When held steady or flashing, it means that a
trouble condition exists on the panel. Trouble conditions are often activated by
a contaminated smoke detector or an electrical problem within the system. Trouble
conditions are also activated by a zone being disabled (disconnected from the system),
a circuit being disabled, low power on the backup battery, the disabling of a notification
appliance, the ground faults, or short or open circuits. Usually the alarm panel's
sounder will activate if a trouble condition exists, though older systems would
sometimes activate a bell or other audible signal connected to the panel. In a trouble
condition, the panel displays the zone or devices causing the condition. Usually,
the "Trouble" indicator goes out automatically when the situation causing the trouble
condition is rectified, however in some systems (EST) the panel must be reset to
clear the trouble alarm. Some panels have more specific indicators such as 'Trouble-PSU'
which shows when the panel itself is compromised and 'Trouble-Bell' ('Sounder fault'
on UK panels) which shows that the sounders are not functioning correctly. On most
panels, an acknowledge button is pressed to turn off the panel's buzzer.
Supervisory
This signal indicates that a portion of the building's fire protection system has
been disabled (such as a fire sprinkler control valve being closed and, consequently,
a sprinkler tamper switch being activated), or, less frequently, that a lower priority
initiating device has been triggered (such as a duct smoke detector). Depending
on the system's design, the supervisory point may be latching, meaning the panel
must be reset to clear the supervisory condition, or non-latching, meaning the indicator
automatically goes out when the condition has cleared. However, some panels require
a reset regardless of whether the supervisory point is latching or non-latching.
AC power
Also known as "Normal". When this indicator is lit, power is being provided to the
system from the building's electrical system, and not from the backup battery. When
an AC power condition changes, the Trouble indicator comes on and the AC power indicator
goes off and the screen alerts building personnel of a power failure. If the AC
power indicator is lit without any other indicators also lit, then the system is
in a normal condition. If no LEDs are lit, there is no power source feeding the
panel.
DC power
This is used to tell the operator that DC power (batteries) are being charged or
used. While using DC power, the system remains in a trouble condition.
High rate
This LED is on when there are unusual power-line conditions.